gototopgototop

Non-perforated tray Hard H=80

.

  Metal cable trays - the electrotechnical product made of the metal structural stock, which are designed for the protection of cables and wires from the mechanical damages of insulation. The trays are produced of the steel galvanized by the Sendzimir method, which secures the long operation life.

 Non-perforated tray Hard
H, height=80 mm

Non-perforated tray Hard H=80 Non-perforated tray Hard H=80 Non-perforated tray

Trays can be ordered with covers
  Non-perforated tray Hard H=80

Example of trays assembling

 
Name Width,
а, mm
Load,
Q, kN/m
Metal
thickness,
mm
Weight*,
kg/pc.
Article Add to calculation
Non-perforated tray H 100х80 100 3,20 1,5 10,24 2123350 м.
Non-perforated tray H 150х80 150 12.01 2124350 м.
Non-perforated tray H 200х80 200 13,78 2125350 м.
Non-perforated tray H 300х80 300 17,31 2126350 м.
Non-perforated tray H 400х80 400 20,84 2127350 м.
Non-perforated tray H 500х80 500 24,37 2128350 м.
Non-perforated tray H 600х80 600 27,91 2129350 м.

*)product weight is not more than, kg.

 Trays are joined using:
   - by joint plate Hard - 2 pcs.;
   - by screws М6х12 - 16 pcs.;
   - by nuts М6 with the incision - 16 pcs.

Standard trays length - 3000 mm.
The trays with the length of 6000 mm can be produced on special order.

Material: steel sheet galvanized with the Sendzimir method. 

Tray
a×H. mm
Useful
cross section, mm2
100х80 7400
150х80 11200
200х80 15000
300х80 22700
400х80 30400
500х80 38000
600х80 45700

Schedule allowable loads for the tray non-perforated Hard H=80 mm